The WRC4-OB5S is a DC Output Module. One in a series of solid-state relays commonly used in industrial applications. The WRC4 package offers the following advantages:

  • Status LED is more easily visible
  • Fuse can be tested and replaced without removing the modules
  • Fuse is a popular CE-rated fuse
  • Popular Euro-style fuse has multiple sources
  • Matches the industry de facto standard footprint
  • Low height convenient for mounting
  • Compact footprint continues to save space
  • Compatible with WRC’s line of SmartMux and data aquisition cards
  • UL and CE marks standard
  • 5, 15 and 24 volt logic available
  • Proven reliable circuitry

  • INPUT 1781-OB5S OC5S Units
    Nominal Input Voltage 5 5 V dc
    Min. Input Voltage @ Pin 3 2.5 2.5 V dc
    Max Input Voltage @ Pin 3 7.5 7.5 V dc
    Must Turn Off Voltage 1.0 2.0 V dc
    Typical Input Current 10 10 mA dc
    Maximum Input Current 27 27 mA dc
    Nominal Input Resistance 240 240 ohm

    OUTPUT OB5S OC5S Units
    Nominal Line Voltage 24 100 V dc
    Maximum Line Voltage 60 200 V dc
    Minimum Line Voltage 3 5 V dc
    Max. Peak Off-state Voltage 60 200 V
    Max. Off-state Leak. Current 1.0 2.0 mA dc
    Maximum On-state Current 3* 1** A dc
    Minimum On-state Current 10 10 mA dc
    Maximum 1 Second Surge 5 5 A peak
    Peak On-state Voltage @ 25°C 1.5 1.5 V peak
    Maximum Turn-on Time 50 50 u sec
    Nominal Turn-on Time 10 10 u sec
    Maximum Turn-off Time*** 100 100 u sec
    Derating Per Degree Above 60°C 33* 20** mA

    • * Derate 33mA/degree above 25°C
    • ** Derate 20mA/degree above 60°C
    • ***With appropriate communicating diode

    CROSS-REFERENCE OB5S OC5S
    Potter Brumfield ODC-5 ODC-5A
    OPTO-22 ODC5 ODC5A
    Grayhill 70-ODC5 70-OAC5A
    Crouzet / Gordos ODC5(F) ODC5A
    Tyco / P&B ODC-5 ODC-5A
    Crydom ODC5(F) ODC5A
    Continental I/O3-ODC-05-A00 N/A
    Analog Devices OD060 N/A
    Dataforth OB5S OC5S

    Application Notes

    • Do not install or remove modules in live (electrically hot) circuits. High voltage may be present.
    • Output connections are polarized.
    • An externally located commutating diode must be installed across inductive loads.