 Part #s
- 3005-17 - Point Sensor Temp/Humidity, 418 MHz
- 3005-115 – Point Sensor Temp/Humidity, 900 MHz
Features – 418 MHz & 900 MHz
- Measures Temperature and Relative Humidity
- Broad operating temperature range
- CRC-16 checked Status, ID, Temperature and %RH
- Conformal coated
- Complies with part 15 of the FCC rules
|
Features – 418 MHz
- Up to 600 foot transmission range
- Transmission rates from 10 to 17 seconds random
- Up to 100 sensors can coexist
- Battery lasts from 2 to 5 years
- Very small (1.3" X 2.1" X .6") ABS Enclosure
- Internal Loop antenna
|
Features – 900 MHz
- Sensirion SHT71 single chip temperature/humidity sensor
- Calibration/linearization data stored in sensor
- Integrated 100mw, 900 MHz SSFH radio for long range performance
- 30-Bit unique ID
- Range Indoor: Up to 1300 feet
- Range Outdoor: Up to 1 mile with standard antenna
-
Battery
lasts up to 2 years at 5 minute transmit intervals (6 years with
optional battery pack)
- Very small
(3.25” X 3.25” X 1.375”) ABS Enclosure
- External ¼ wave antenna with RPSMA connector (Optional antennas
available)
|
Description
The Point Sensor Wireless Temperature and Relative Humidity sensor is a battery
operated digital temperature and relative humidity sensor with a microprocessor
controlled 418 or 900MHz. FCC certified radio transmitter. The Point Sensor
Temp/Humidity sensor has an on board time of day clock which allows it to spend
most of the time in a low power quiescent state. At predetermined time intervals
the clock will wake up the onboard microprocessor. Unique serial number
information, linearized temperature, linearized and temperature compensated
humidity data are combined with a CRC-16 error check and transmitted in a very
short data packet which results in a very short transmitter on-time. This
architecture allows the Point Sensor Temp/Humidity sensors to consume very low
energy resulting in a battery life of up to 2 years (900 MHz) or up to 5 years
(418 MHz).
The electronics are coated
with a conformal material which provides a moisture barrier against condensation;
however, submersion in water is not recommended. The service switch is
activated by either inserting a special tool through a hole in the top ABS cover
(418 MHz), or a magnet activates an internal read switch (900 MHz). The Sensor
is shipped with the transmitter turned off (anytime the Sensor is to be shipped
the transmitter should be turned off or must be placed in a shielded container
to prevent interference that might cause shipping problems). Start the Sensor
by either momentarily pushing the service switch, you will feel the button click
(418 MHz); or by loosening the lid screws, removing the battery pull tab, and then
swiping a magnet across the enclosure on the side opposite the antenna (900 MHz). When
the Sensor starts, a data transmission occurs immediately and a special mark is
introduced in the ID field of the transmitted data packet to indicate which
sensor is in service or installation. The service switch and the battery pull
tab are also used to put the Sensor in a quiescent mode (no transmissions and
very low power consumption). This is the state the Sensor is in when you receive
it from the manufacturer. Push and hold the service switch (418 MHz) for 5
seconds or more; or remove the batteries or reinstall the pull tab (900 MHz) to
enter this powered down state.
|
Frequency |
418 MHz |
900 MHz |
|
Transmission rate |
10-17 seconds random |
5 minutes |
|
Shelf life with battery installed |
5 Years in quiescent mode |
10 Years in quiescent mode |
|
Dimensions (enclosure) |
1.5 W X 2.1 H X .6 D (inches) |
3.25 W X 3.25 H X 1.375 D (inches) |
|
Weight |
1.5 oz. |
4.7 oz. |
|
Storage Temperature |
-40° to 70° C |
-40° to 85° C |
|
Operating Temperature |
-40° to 70° C |
-40° to 85° C |
|
Temp. Accuracy (-10° to 85° C) |
+/-0.5° C |
+/-.4° C |
|
Humidity |
0% to 100% non-condensing |
0% to 100% non-condensing |
|
Humidity Accuracy |
+/-5 % Full Scale (25° C) |
+/-3% (20% to 80%) |
|
Battery life with transmissions
|
2-5 years with TX period of 10-17 sec. |
2 years with TX period of 5 min. |
|
Battery |
3.6 volt Lithium |
(2) 1.5 volt Lithium (Energizer L91) |
|
FCC Certified |
FCC ID: M5ZWOWTHL |
FCC ID: OUR9XSTREAM |
|