 Part # - 3005-105 - Universal Output Module, 900 MHz
Features
- Performs counter-in, analog/relay-out and repeater functions simultaneously.
- Integrated 100mw, 900 MHz SSFH radio for long-range performance.
- Outputs voltage, current and form-C relay status from remote sensors.
- Acts as a 900 MHz. pulse counter.
- Built-in 900 MHz. packet repeater functions.
- Learns sensor device IDs from unique packet serial numbers.
- 30-Bit unique ID on UOM (counter) packets.
- CRC-16 error checked on all packet transfers.
- Range Indoor: Up to 1300 feet.
- Range Outdoor: Up to 1 mile with standard antenna.
- 12-24VDC power.
- Very small (3.25” X 2.5” X 1.125”) ABS Enclosure.
- External ¼ wave antenna or internal wire.
Description
The Universal Output Module (UOM) provides analog output in both voltage and
current forms as well as discrete form-C relay output. The UOM also acts as a counter,
producing standard Point Six radio data packets as a single input counter accumulating
active state time and number of activations of a switch closure input. Also,
the UOM acts as a standard packet repeater for all Point Six 900 MHz. radio data
packets. The UOM is married to Point Sensors with a simple ID-learn-sequence that
stores sensor IDs in EEPROM so that the UOM knows which devices source the analog
and discrete outputs. The UOM can be married to a single analog source and a single
discrete source device at the same time while also producing counter device packets
and repeating 900 MHz. packets from other Point Six devices. Analog output
is produced in both voltage (0-5V or 0-10V) and current (0-20mA. or 0-40mA) at the
same time with a common ground. The high/low analog output range is controlled
by internal jumper selection and is shipped in the low range (0-5V, 0-20mA) mode.
The relay output is an isolated form-C with 2-Amp contacts. The counter input
is self-excited with 5V at 1 mA. referenced to the same ground as the analog
outputs and the power input. This common ground architecture allows the UOM
to be substituted for current mode sensors in 4-20 mA. remote applications.
The electronics are coated with a conformal material that provides a moisture
barrier against condensation. Submersion in water is not recommended.
An internal pushbutton switch permits a user to activate the ID-learn-sequence and
service mode functions.
| Analog output |
12-bit resolution 0-5 or 0-10 V and 0-20 mA or 0-40 mA. |
| Relay output |
0.5 A at 125 VAC 2 A at 30 VDC |
| Switch closure input |
5V at 1 mA short circuit, .01sec. minimum active (closed) time |
| Storage Temperature |
-40° to 85° C |
| Operating Temperature |
-40° to 85° C |
| Dimensions (enclosure) |
3.25 W X 2.5 H X 1.125 D (inches) |
| Weight |
4 oz. |
| Radio FCC Certified |
FCC ID: OUR9XSTREAM |
| Power |
12-24Vdc 200 mA. |
|