 Part #s
- 4006-26 - Point Manager, 418 MHz
- 4006-24 - Point Manager, 900 MHz
- 4006-34 - Point Manager, 418 MHz & 900 MHz
Features
- 418 MHz, 900 MHz , or both 418 MHz & 900 MHz Receiver
- Supports all Point Sensors
- Communicates: Ethernet (TCP/IP) and/or serial port
- Data Logger – logs periodic snapshots of the current readings & logs events
- Web Server – Dynamic HTML web page server showing current readings and alarms
- Event based alarms – callout or email
- Push connection to other hosts using TCP/IP based on alarms
- Optional Push connection to web server and post History and Event Records
via XML records
- Simple ASCII command/response protocol
- 100 Sensors (total of 250 I/O points)
maximum
- 15000 Historical Record capacity
- 14000 Event Logging capacity
- Two level password security
- Each I/O configurable to trigger events
- Periodic callouts with interval times of 1 minute to 7 days
Description
The Point Manager is a RF receiver with
an integrated data Web Manager. It receives CRC-16 error-checked data packets
from Point Six’s sensors, processes the data, and makes the data available to be
queried by simple ASCII commands or through dynamic HTML. The dynamic HTML can be
viewed with any standard browser. The Point Manager communicates with a PC using
TCP/IP or serial protocol. Simple ASCII commands are sent over the Ethernet
using TCP/IP and/or RS232 serial port. The Point Manager contains a time of day
clock, battery backed RAM, and flash programmable memory. It is fully configurable,
both locally and remotely. It can store configuration information for up to
100 sensors having a combined maximum of 250 I/O points.
The Point Manager was built with the flexibility needed to satisfy varied user
requirements. There are several modes of operation that allow the user to
balance simplicity, costs, precision, and timeliness.
Monitoring - The easiest way to get information from the Point Manager
is to view the current sensor values. This can be accomplished with a Web
browser (no software coding required) or polling by a host. Both alarms and
data are available.
The dynamic HTML page displays on each row the following sensor information:
name, serial number, age since last reception, service mode indicator, readings
and units. All readings are shown in engineering units.
Collecting – Snapshots of the current sensor values can be periodically
stored in a Historical Log. The snapshots can be retrieved for later analysis.
All configured sensors readings are used in the snapshot. The snaps can be
taken from once a minute to once every 7 days. The Point Manager can be thought
of as a remote data logger.
Concentrating – Key changes in a sensor reading, sensor age or system
parameters can trigger records to be logged into an Event Log. The following
items can be configured to trigger events: Point Manager startup, Historical Log
% full, sensor age, sensor service button, analog I/O high/low thresholds, counter
I/O base count and interval, and state change. The Point Manager stores a
time stamp with the event. Approximately 1800 events can be stored in the
Event Log. Also when an event is triggered, the Point Manager can optionally
take a snapshot of the current sensor readings and store it in the Historical Log.
Notifying – Each event can be configured to trigger the Point Manager
to notify a host. The Point Manager can notify a host either pushing a connection
through the Ethernet (TCP/IP) or serial port. The host computer then does
not need to be always connected and polling the Point Manager. The Point Manager
can inform the host of the exceptions by establishing the connection. The
Point Manager can be configured to notify up to 5 host destinations trying each
destination until the event is confirmed delivered. The Point Manager can
also send alarms via SMTP email through the Ethernet.
The Point Manager is a data logger that can be used to store data while the Point
Manager is not connected to a host computer. The data-logging feature can
be used as a backup in case communications is lost through the Ethernet or serial
connection. The Historical Log and the Event Log are circular. If either
becomes full, the next record will overwrite the oldest record. CRC16 error
checks are added to the simple ASCII commands and response when using the local
serial port.
As an option, the Point Manager can initiate a connection to a host web server
at regular intervals or when an alarm occurs and can deliver (via HTTP Post) XML
files. The XML files contain History and/or Event records. The XML files
can then be easily posted to a database. This mechanism makes it possible
to install the Point Manager behind a firewall without changing the setup of the
firewall.
The Point Manager can be easily configurable using ASCII commands. Each
sensor can be given a label name and setup information for each I/O point such as
engineering scale and offset, units label, and alarm trigger information.
The Point Manager has a “media callout table” where the user can specify which host
destinations the Point Manager is going to connect for notification by either serial
or Ethernet. The Point Manager can also be configured to callout periodically
with interval times from once a minute to once every 7 days.
The Point Manager has optional security through two levels of login passwords:
one for access to data and setup information and the other for changing the setup
information.
|